My main website www.cfn-hvac.com
HVAC approach for HVDC application.
A high-voltage, direct current (HVDC) electric power transmission system uses direct current (DC) for the bulk transmission of electrical power
HVDC (high voltage DC supply) is mainly used for long distances to minimise power loss.The converter/rectifier hall is 1 big faradays cage designed hall with no entry to personnel during normal operations.All indoor M&E equipment must be grounded.Only ventilation is required except for high temp regions like the gulf.N+2 configuration for redundancy.AHU sections. Heating coil, humidifier, pre-filter + bag filter.100 % fresh air with 30 Pascals pressurisation and with gravity release dampers at upper levels of the converter hall.Interior design Maximum 48 C minimum 5 C, maximum supply temp. 40c and minimum at 10c, maximum Relative humidity 60% and minimum 30%Heat losses on Average 300 KW, including Process piping.500 Lux uniform Lighting.For security, entrance doors are interlocked for power shutdown in case of fire.Fire fighting, manual extinguishers at entry and automatic interior extinguishing on the interior for the controls room.BMS, all sensors High Temp & Low temp, high & low humidity etc... to connect to Controls room.I can be consulted on this and help you achieve your goals Remotely.